Tier 3 is the third level of a four-level classification that describes how redundantly a data center's infrastructure is built. A Tier 3 data center has several independent supply paths for power and cooling and can be maintained without switching servers off. Maintenance work or the failure of a single component does not interrupt operation.
Key facts
- Classification
- Tier I to Tier IV
- Key feature
- Maintenance during operation
- Redundancy
- At least N+1 for power and cooling
- Versus Tier 4
- Fault-tolerant, two active supply paths
- Location
- Velbert (DE-VEL), carrier-neutral, built to Tier 3 standard
- Operator
- NETMOUNTAINS
Where does the tier classification come from?
The classification comes from the Uptime Institute. It rates the building infrastructure, meaning power, cooling and their distribution. It says nothing about servers, support or network connectivity. Tier I has a single supply path without redundancy, Tier II has redundant components but still only one path. Tier III has several independent paths and can be maintained during operation, Tier IV is fully fault-tolerant. There is a difference between formal certification by the Uptime Institute and the far more common use of the term to describe how a facility is built.
What does Tier 3 mean in operation?
The technical term is concurrently maintainable. Every component of the supply can be switched off, serviced or replaced without shutting down IT systems. Replacing UPS batteries or the annual generator service therefore needs no maintenance window. This requires at least N+1 redundancy: there is always one more unit than operation needs. If a component fails, the reserve takes over without manual intervention. The following are typically built redundantly:
- Power supply: several feeds, UPS systems and a backup generator with a fuel reserve.
- Cooling: several chillers and air conditioning units, any one of which may fail.
- Distribution: separately routed power paths into the rack, servers with two power supplies.
- Network connectivity: several carriers and structurally separated fibre feeds.
- Security systems: early fire detection, extinguishing system, access control and video surveillance.
What matters is less the number of devices than whether the supply paths really run independently of each other.
Difference between Tier 3 and Tier 4
Tier III has one active and at least one additional supply path. If a fault occurs, a switchover may be needed that is briefly noticeable. In Tier IV, two physically separated paths are active at the same time and a single defect does not affect the IT. This needs twice the equipment and twice the floor space, and energy use goes up. Hosting, web applications and corporate IT therefore usually run in Tier III facilities. Tier IV is built mainly where an outage would have immediate, serious consequences.
What does "Tier3+" mean?
"Tier3+" is not a level defined by the Uptime Institute but a sales term. It usually refers to a data center that meets Tier III and goes further in individual trades, for example with 2N redundancy in the power supply or extra cooling reserves. Because the term is not standardised and often not backed by a certification, it says little on its own. Ask specific questions instead:
- Which trades are built redundantly, and how (N+1 or 2N)?
- Is there a certification or an audit report, or is it a self-description?
- How often is the backup generator tested under load?
- What availability does the provider guarantee in the SLA?
- Is the data center carrier-neutral or tied to a single network operator?
What this means for your server's availability
Whether your server is reachable depends on hardware, network and building together. A server with two power supplies helps little if there is only one power rail or the air conditioning has to be switched off for maintenance. Tier III ensures that maintenance on the building does not affect customer systems. Realtoxmedia runs its systems in the DE-VEL data center in Velbert. It is operated by NETMOUNTAINS, carrier-neutral, built to Tier 3 standard and designed with 2N redundancy on site. A contractual availability of 99.95% applies to Cloud Servers.
Carrier neutrality
A carrier-neutral data center does not belong to a network operator and lets several providers into the building. The operator can combine connections freely, and the failure of one carrier does not affect the whole facility. The tier level says nothing about this, as it only rates power and cooling. Check both separately: the building via the tier rating, the network via the provider's autonomous system.
Tier 3 means several independent supply paths and maintenance without shutdown. "Tier3+" is a sales term. Ask which trades are redundant, whether a certification exists and what availability is guaranteed in the contract.