What does redundancy mean in a data center, and what is 2N?

In short

Redundancy means that a data center keeps more capacity available for every critical supply than operation requires, so that a failure or maintenance work does not reach the servers. 2N means that the entire required capacity (N) exists twice, each with its own supply path. If one side fails completely, the other carries the full load on its own.

Key facts

N
Capacity that operation needs at minimum
N+1
One additional spare unit
2N
Entire capacity twice, on two separate paths
2(N+1)
Two separate paths, each with its own spare
Limit
Ends at your server's power supply
Velbert (DE-VEL)
Power, cooling and network 2N redundant

What does a data center have to safeguard?

At its core, a data center is a supply facility for servers. They need uninterrupted power, their waste heat has to be removed, and without network connectivity they are useless. Each of these supplies can fail and has its own technology. This includes:

  • The power feed from the public grid and its distribution to the rack.
  • The uninterruptible power supply (UPS), which bridges a grid failure with batteries until the generators are running.
  • Generators with a diesel reserve, which take over the load during longer outages of the public grid.
  • Cooling with chillers and air conditioning units.
  • Network connectivity via several carriers, separate fibre routes and redundant routers.
  • Access control, video surveillance, early fire detection and fire suppression.

Access and fire protection are not counted in redundancy levels, but they help decide whether operation continues. For power, cooling and network, the terms N, N+1 and 2N describe how much reserve is available.

N and N+1

N stands for the number of units needed to carry the full load. If the servers in a room need four air conditioning units, N equals 4. With exactly N units, every defect leads to an undersupply and every maintenance job requires a shutdown. N+1 adds one spare unit, so in the example five units for a load of four. One unit may fail or be serviced without the servers noticing. The limit of N+1 lies in the shared path: if all units hang on the same distribution or the same pipework, the spare does not help when exactly that path fails. In addition, no reserve is left while one unit is being serviced. N+1 is therefore regarded as the minimum for professional operation.

2N and 2(N+1)

With 2N the full capacity exists twice, split across two separate systems that are often called the A and B side. Each side has its own UPS, its own distribution and usually its own generators. Servers with two power supplies are connected to both sides at once. A whole side may fail or be shut down for maintenance while the other carries the load alone. For a load of four units, eight are therefore available, in two strings of four. 2(N+1) goes one step further and gives each side its own spare as well, in the example two times five units. Then one unit on the other side can still fail even while one side is being serviced. Costs rise with every level, because with 2N each unit runs at no more than half load in normal operation.

Redundancy level and Tier rating

The Uptime Institute's Tier classification uses these terms but is not the same thing. It also assesses whether the supply paths run independently of each other and whether the building can be maintained during operation. What Tier 3 specifically requires and how it differs from Tier 4 is explained in the article on Tier 3 data centers. What matters in practice: redundancy can be designed differently for each system. A statement such as "redundant power supply" says little without a level. Ask separately for power, cooling and network which level applies and whether the paths are physically separated.

Where the data center's redundancy ends

The building's redundancy protects the supply up to the rack. What happens after that depends on the server and on you. A 2N data center does not prevent an outage whose cause lies in the server itself or in the software. Typical gaps are:

  • A server with only one power supply hangs on a single side and goes down if that side is switched off.
  • Mainboard, memory or drives can fail without power or cooling being involved.
  • A faulty update, a full disk or a wrong configuration takes the service down, even if the building is running perfectly.
  • Redundant storage copies errors as well. A deleted folder or an encryption attack hits every copy in a RAID array or storage cluster equally.

The only protection against data loss is therefore a backup that is stored separately from the system and keeps several versions.

Redundancy and high availability

High availability describes the goal that a service stays reachable. Redundancy in the data center is one building block for this, but it is not enough on its own. A highly available setup also duplicates the layer above: several servers or hosts, distributed storage and automatic failover. With virtual servers the provider often takes care of this by storing the data in a distributed storage cluster and restarting a virtual machine on other hardware if a host fails. With dedicated servers and colocation you build high availability yourself, for example with two servers, a load balancer or cluster software. If both systems are in the same data center, the building's redundancy protects you. Only a second site helps against the loss of the entire location.

At Realtoxmedia, power, cooling and network connectivity in the Velbert data center (DE-VEL) are 2N redundant, backed by UPS and backup generators. The site is built to Tier 3 standard. A contractually guaranteed availability of 99.95% applies only to Cloud Server, whose data is stored in the Ceph cluster.

Bottom line

N+1 keeps one spare unit in reserve, 2N duplicates the entire supply on two separate paths. This redundancy protects the supply up to the rack, but not your server, your software or your data. For a highly available service you also need redundant systems and backups on your side.